Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/18/2026 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Re-inspection required | 9/18/26: expose/excavate 2'x2' pockets at each end of bedroom & laundry room in order to verify footing depth, remove all drywall from the bedroom walls, laundry room and above ceiling to verify framing, AWG wires, anchor bolts, Simpson clips, and duct work. The plumbing at the laundry room shall be placed under test to verify no leaks and hammer arrestors at laundry will be required together with insulation on the hot copper line of water heater. Arch fault breakers are required for habitable areas and gfci receptacles are required within 6' of water. A letter from a licensed contractor shall be submitted to the City of Tucson for review & approval. The contractor's letter must document that all roof construction meets requirements of the 2018 IRC. | |
| 10/16/2026 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Passed | 10/16/2026 Verified all construction within scope of work per 2018 IRC. Verified main service panel for AFCI and GFCI protected circuits. Received letter from licensed contractor and was unloaded into TDC online portal. |