Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/22/2026 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 6-22-26: see previous notes from 6/15/26. A revision is required for roof plans showing change of rafter layout and use of ledger and hangers. Current configuration has rafters running east/west using hangers and j-bolts only on the east wall, however plans call for rafters to run north/south and use of top plate with clips and embedded j-bolts according to detail 4 & 5. Additionally, anchor bolts at exterior walls are required within 12" at the ends of each plate and a minimum of 2 shot pins are required within 6" at the ends of a sill plate on non bearing partition walls. | |
| 10/16/2026 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | 10/16/2026 Verified revised plans and corrections made. |