Permit: TC-RES-0725-03465

Parcel: 135090550


Addresses:

1716 S 29TH PL

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
03/27/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 3/19/26: exterior sheathing must be properly fastened with approved fasteners (per IRC T602.3), vapor barrier must be removed to verify sheathing, h2.5 clips must be properly fastened throughout, blocking required at soffits, nm cables shall be properly secured every 48", pex shall be properly supported at intervals not to exceed 32" horizontal and 48" vertical, pvc required plastic strapping, mechanical flex shall be secured at intervals not to exceed 5' o.c, nail plates and Boca plates required throughout where rough-ins come closer than 1 1/4" from face of framing member, seal all penetrations throughout at top plate and vapor barrier. STOPPED INSPECTION MORE ITEMS MAY BE ADDED

3/25/26 DVW not on test, insulate pex lines in uninsulated garage, missing nail plates for pex lines in kitchen area
3/27/26: Pex must be insulated at garage, hot water lines 3/4" and larger shall also be insulated, 12" clearance from can lights required, properly support pex lines throughout, seal off flex duct joints. Per previous notes
04/01/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Canceled
04/30/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed