Permit: TC-RES-0725-03316

Parcel: 136250180


Addresses:

6665 E 38TH ST

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
04/13/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 4/13/26
1. Window at guest bedroom is too high needs to be 44 inches maximum.
2. Truss R14 is a 3ply and needs to be carried by (3)2x6, currentlycurrently you have (2)2x4 carrying the load on the south wall.
3. Cracked roof rafter on the north end just above kitchen window, I marked with an arrow.
4. Truss R03 needs to be carried by (2) 2x6.
04/28/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed