Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Parcel: 12912232A


Addresses:

1031 E 32ND ST


Inspection Status: Not Ready

Inspection History: COT - RSEL - Electrical Final 

Permit Number - TC-RES-0724-04336

Inspection Description - COT - RSEL - Electrical Final 

Inspection Status - Not Ready

Date Description Inspector Results Comments
10/16/2025 COT - RSEL - Electrical Final  Not Ready All receptacles have to be gfci protected. Lighting has to be on a separate circuit from gfci at lav. Provide updated panel schedule. Underground electrical had to be a minimum of 18" deep to the top of pipe and rises either have to be schedule 80 or rigid conduit. 10/16/2025