Inspection Status: Not Ready

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Permit Number - TC-RES-0724-04290

Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Inspection Status - Not Ready

Date Description Inspector Results Comments
04/09/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Not Ready Framing incomplete. Loose osb. Nailing not per schedule. Add blocking to seams. 4/9/2025
04/15/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 4/15/25
1. All anchor bolts had loose nuts.
2. Missing anchor bolt within 12" of splice on south wall
3. Shot pins required within 6" of edge sill plate and every 2' after , I have marked with an x circle.
4. Porch framing not per plan; Beam needs to be 6x10.
5. Handicap blocking needed at bathrooms see page S-2 for details.
6. Porch Beam and post caps not per plan.
08/01/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required Framing incomplete. Loose osb. Nailing not per schedule. Add blocking to seams. 4/9/2025

4/15/25
1. All anchor bolts had loose nuts.
2. Missing anchor bolt within 12" of splice on south wall
3. Shot pins required within 6" of edge sill plate and every 2' after , I have marked with an x circle.
4. Porch framing not per plan; Beam needs to be 6x10.
5. Handicap blocking needed at bathrooms see page S-2 for details.
6. Porch Beam and post caps not per plan.

8.1.25
Multiple items remain uncorrected
08/26/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 8.26.26
Corrections ,add as requested, beam verified via provided note
Approved