Parcel: 14025107B


Addresses:

1137 E BILBY RD


Inspection Status: Re-inspection required

Inspection History: COT - RSPL - Gas Pressure Test 

Permit Number - TC-RES-0724-04287

Inspection Description - COT - RSPL - Gas Pressure Test 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
11/03/2025 COT - RSPL - Gas Pressure Test  Re-inspection required 11.03.2025
Seal top plate penetrations throughout with fire foam, add smoke detector in primary bedroom & hallway, ground metal pancake boxes, brace DWV line midway in water closet and laundry area. Subpanel in utility room cannot be closed off and gas and condensate lines underneath panel will need to be routed above or away from panel - ensure shutoff valve access to gas as well. Refer to E3405.1 of 2018 IRC or 110.26 of NEC 2017 for code details.
12/17/2025 COT - RSPL - Gas Pressure Test  Passed 12/17/2025
Approved and holding under test.