Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
Permit Number - TC-RES-0724-04286
Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 3/25/25: H3 clips missing throughout per detail 201 and 202, DTC Clip required at 36" o.c at interior non-bearing wall, shot pins at interior non-bearing required 48" o.c and within 4" of sill plate, shear-wall fasteners not per schedule 6" o.c at edge and 12" o.c at field. STOPPED INSPECTION MORE ITEMS MAY BE ADDED. | ||
| 03/27/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | 3/27/25 corrections made |