Inspection Status: Re-inspection required
Inspection History: COT - BULD - SWG Clearance
| Date |
Description |
Inspector |
Results |
Comments |
| 01/17/2025 |
COT - BULD - SWG Clearance |
|
Re-inspection required |
New gas line not installed at hot water heater, no sediment trap on gas line, gas line not properly supported; needs to be installed inside of rear or side wall to protect from damage. Gas meter is in the alley at the southwest corner of property; appears that gas line maybe running underneath storage building in southwest corner of backyard. Storage building is not shown on site plan. |
| 01/22/2025 |
COT - BULD - SWG Clearance |
|
Not Ready |
1-25-22, not ready-not under pressure. Must be set at 15psi for a minimum of 10 minutes. |
| 01/24/2025 |
COT - BULD - SWG Clearance |
|
Re-inspection required |
1-24-25, pex lines were ran directly to the gas water heater-see ch. 28 of the international residential code for additional information/code requirements. Missing pressure relieve valve, catch pan, and no condensation line extending to the exterior |
| 05/16/2025 |
COT - BULD - SWG Clearance |
|
Passed |
5/16/25 corrections made CLEARANCE SWG |