Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - BULD - SWG Clearance
Permit Number - TC-RES-0724-04183
Inspection Description - COT - BULD - SWG Clearance
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/17/2025 | COT - BULD - SWG Clearance | Re-inspection required | New gas line not installed at hot water heater, no sediment trap on gas line, gas line not properly supported; needs to be installed inside of rear or side wall to protect from damage. Gas meter is in the alley at the southwest corner of property; appears that gas line maybe running underneath storage building in southwest corner of backyard. Storage building is not shown on site plan. | |
01/22/2025 | COT - BULD - SWG Clearance | Not Ready | 1-25-22, not ready-not under pressure. Must be set at 15psi for a minimum of 10 minutes. | |
01/24/2025 | COT - BULD - SWG Clearance | Re-inspection required | 1-24-25, pex lines were ran directly to the gas water heater-see ch. 28 of the international residential code for additional information/code requirements. Missing pressure relieve valve, catch pan, and no condensation line extending to the exterior |