Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/02/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | Missing shear walls throughout. Provide anchor bolts at center third of bottom plates. Loose bolts throughout. Add pins 6" from edges and every 24" o.c. Cross bracing not per plan. Nails shall not penetrate more than 1/8". 7/2/2025 | |
| 07/03/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | Missing shear walls throughout, anchor bolts at shear walls not per plans. Provide anchor bolts at center third of bottom plates. Loose bolts throughout. Add pins 6" from edges and every 24" o.c. Cross bracing not per plan. Nails shall not penetrate more than 1/8". 7/2/2025 7/2/25: per previous notes. not ready |
|
| 07/07/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required (with fee) | 7-7-25: a/b required at 32" o.c. on exterior walls. Braced panel requires 4 a/b's per panel, add shot pins at marked locations, anchor bolts are required within 12" of a splice on each side, missing nails on exterior sheathing at /edges-joints throughout, loose roof panels-have framer walk entire roof and add nails accordingly. | |
| 07/08/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | 7-8-25: exterior clips/sheathing approved. Okay to continue with construction. |