Permit: TC-RES-0724-04094

Parcel: 119411550

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
07/02/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required Missing shear walls throughout. Provide anchor bolts at center third of bottom plates. Loose bolts throughout. Add pins 6" from edges and every 24" o.c. Cross bracing not per plan. Nails shall not penetrate more than 1/8". 7/2/2025
07/03/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required Missing shear walls throughout, anchor bolts at shear walls not per plans. Provide anchor bolts at center third of bottom plates. Loose bolts throughout. Add pins 6" from edges and every 24" o.c. Cross bracing not per plan. Nails shall not penetrate more than 1/8". 7/2/2025

7/2/25: per previous notes. not ready
07/07/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required (with fee) 7-7-25: a/b required at 32" o.c. on exterior walls. Braced panel requires 4 a/b's per panel, add shot pins at marked locations, anchor bolts are required within 12" of a splice on each side, missing nails on exterior sheathing at /edges-joints throughout, loose roof panels-have framer walk entire roof and add nails accordingly.
07/08/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 7-8-25: exterior clips/sheathing approved. Okay to continue with construction.