Permit: TC-RES-0724-03990

Parcel: 13219059D


Addresses:

4715 S BENTLEY AV

Inspection Status: Passed

Inspection History: COT - RSBU - Roof NailingĀ 

Date Description Inspector Results Comments
01/08/2025 COT - RSBU - Roof NailingĀ  Passed Corrections made, roof nailing and trusses per plans. anchor bolts not per schedule, check t intermediate, owner states will be done at that time. Ok to proceed to intermediate
12/11/2024 COT - RSBU - Roof NailingĀ  Re-inspection required 12/11/24: Anchor bolts required at 32" o.c at perimeter load bearing walls (throughout), anchor bolts required 12" from edge of sill plate, 2x8 Nailer required per plans throughout (key note 9 on framing), truss clacs required for inspection, roof access required. Shot pins required at interior no bearing walls throughout.