Parcel: 140241760


Addresses:

1542 E GINTER RD


Inspection Status: Re-inspection required

Inspection History: RSBU - Building Final 

Permit Number - TC-RES-0723-06836

Inspection Description - RSBU - Building Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
05/12/2025 RSBU - Building Final  Re-inspection required 5/12/25: bubble covers required for outdoor receptacles, all exterior receptacles must be WR receptacles, Hose bibs must be fully insulated and wrapped with UV protected tape, Mini splits must be (M1403.1 Heat pumps. Electric heat pumps shall be listed and labeled in accordance with UL 1995 or UL/CSA/ANCE 60335-2-40.), refrigerant lines must be covered and wrapped for UV protection, all condensate drains must be properly terminated and coated for UV protection, Electrical panels must be properly labeled, Arc-fault breaker's missing throughout, open spaces at dead front must be covered, exhaust fans missing at bathrooms, The majority of receptacles are improperly wired, GFCI receptacles missing at kitchen/exterior/laundry room, mini splits are missing disconnect boxes, anti tip missing at range, porch light must be properly installed on box and properly secured.STOPPED INSPECTION MORE ITEMS MAY BE ADDED.
08/13/2025 RSBU - Building Final  Passed
12/09/2024 RSBU - Building Final  Not Ready