Inspection Status: Partial Pass

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
01/27/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Partial Pass 1-27-25, partial pass. Add nails to marked location at northwest exterior sheathing-Plans call for 4" o.c. At edges.
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Not Ready 2/7/25 add nails to truss hangers where marked, hangers also require nails at 45 degree on the sides as per schedule. Anchor bolts not torqued down, re walk and tighten.
03/04/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 3/4/25 corrections made
11/05/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Not Ready