Inspection Status: Re-inspection required
Inspection History: COT - RSEL - Electrical Underground
| Date |
Description |
Inspector |
Results |
Comments |
| 04/03/2024 |
COT - RSEL - Electrical Underground |
|
Re-inspection required |
Not present. |
| 04/17/2024 |
COT - RSEL - Electrical Underground |
|
Re-inspection required |
Not ready. Schedule 40 has been de valued due to heating element at the bend. Schedule 40 is in place. Plans call for schedule 80. Needs proper depths in some areas. Revision can be made while pursuing at own risk due to the risers needing to be schedule 80 at main panel or rigid metal. 4/17/2024 |
| 05/06/2024 |
COT - RSEL - Electrical Underground |
|
Passed |
|