Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.

Permit Number - TC-RES-0723-06497

Inspection Description - COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
09/07/2023 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Re-inspection required 9/7/23: seal all penetrations through top plate, small appliance receptacle at kitchen missing, nail plate at dryer vent missing, missing nail plate at kitchen hood vent. STOPPED INSPECTION MORE ITEMS MAY BE ADDED
09/11/2023 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Passed 9/11/23: Mechanical, plumbing, and electrical rough-in is complete. Outlet has been added in kitchen at the 9" counter location. Okay to insulate, drywall, tape, texture, and paint interior walls.