Inspection History: RSBU - Building Final 

Date Description Inspector Results Comments
01/06/2026 RSBU - Building Final  Not Ready
02/17/2026 RSBU - Building Final  Passed
12/18/2025 RSBU - Building Final  Canceled
12/19/2025 RSBU - Building Final  Canceled 12-19-25: canceled by contractor.
12/23/2025 RSBU - Building Final  Re-inspection required 12.23.25
Missing receptacles required per code at counter top spaces greater than 12 inches.
Minimum 2 GFCI circuits at kitchen area
Receptacle under sink is required to be GFCI
Light fixture not working at kitchen

Fastener at equipment cannot be drywall screw, minimum 32 threads
Missing receptacle at laundry room per plan
The receptacle that does exist at laundry is not GFCI as required
Exhaust fan missing at laundry per plan
Hammer arrest it's missing at laundry
T&P line required to be copper and terminate outside per plan

Receptacle missing by laundry door per plan

Receptacle spacing at living room not per code
Thermostat required to be at no greater than 48 per city inclusive design

Bathroom threshold height and vertical does not need code. No greater than half inch with bevel required

Receptacle spacing at south bedroom does not meet plan/code

Smoke detectors are not hardwired together

Receptacle missing per plan at west/bedroom 1

Hot and neutral reversed at primary bath
Receptacle missing on opposite counter side primary bath

Repair and seal penetrations at exterior stucco area on south side
Exterior light fixtures cannot have light exposed higher than 45 degrees. (Glass bubbles not per code)

Secure grounding conductor at panels
Arc fault breakers required at all circuits that service livable areas

Water heater breaker requires lockout tag out.
Improper breaker type as per panel specifications
Improper breaker/circuit count at panel
Exterior piping must be glued and painted