Inspection History: COT - RSBU - Roof Nailing
Permit Number - TC-RES-0624-03791
Inspection Description - COT - RSBU - Roof Nailing
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/16/2025 | COT - RSBU - Roof Nailing | Re-inspection required | Missing Htt4 holdowns per schedule. Loose anchor bolts throughout. Missing nuts and washers and bolts. Two pins required at bottom plate greater than 12" and 6" from edges. Add anchor bolts throughout no more than 12" from edges. Add nails throughout at shear walls being penetrated more than 1/8". Interior shear wall nailing not per schedule. Connection from beam to post not per plan. Missing nails at post cap. Stopped inspection other items may occur. 6/16/2025 | |
| 06/18/2025 | COT - RSBU - Roof Nailing | Re-inspection required | 2025 6-18-25: roof inspection only-rewalk roof and add nails add marked area. Loose roof panel at garage -not marked. Reinspection required. |
|
| 06/23/2025 | COT - RSBU - Roof Nailing | Passed |