Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Roof Nailing 

Permit Number - TC-RES-0624-03791

Inspection Description - COT - RSBU - Roof Nailing 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
06/16/2025 COT - RSBU - Roof Nailing  Re-inspection required Missing Htt4 holdowns per schedule. Loose anchor bolts throughout. Missing nuts and washers and bolts. Two pins required at bottom plate greater than 12" and 6" from edges. Add anchor bolts throughout no more than 12" from edges. Add nails throughout at shear walls being penetrated more than 1/8". Interior shear wall nailing not per schedule. Connection from beam to post not per plan. Missing nails at post cap. Stopped inspection other items may occur. 6/16/2025
06/18/2025 COT - RSBU - Roof Nailing  Re-inspection required 2025

6-18-25: roof inspection only-rewalk roof and add nails add marked area. Loose roof panel at garage -not marked. Reinspection required.
06/23/2025 COT - RSBU - Roof Nailing  Passed