Permit: TC-RES-0624-03422

Parcel: 134050910


Addresses:

9323 E MAGDALENA RD

Inspection Status: Re-inspection required

Inspection History: COT - RSPL - Plumbing Final 

Date Description Inspector Results Comments
10/31/2024 COT - RSPL - Plumbing Final  Re-inspection required 10/31/24: GFCI required at Dishwasher, water hammer arrestor required at dishwasher, anti tip required at range, receptacle at laundry room required to be GFCI, water hammer arrestor required at laundry, exterior receptacle by water heater malfunctioning, Pressure relief valve shall terminate no higher than 6" or 2X the pipe diameter, water heater vents must be installed, ARC-fault breaker's required throughout at main panel, dryer vent must terminate with damper at T-top, provide access to roof.
11/04/2024 COT - RSPL - Plumbing Final  Re-inspection required 11/4/24: No access to house, called contractor and left message no answer. Needs to be rescheduled.
11/15/2024 COT - RSPL - Plumbing Final  Passed pass