Inspection Status: Re-inspection required
Inspection History: COT - RSME - Mechanical Final
| Date |
Description |
Inspector |
Results |
Comments |
| 10/31/2024 |
COT - RSME - Mechanical Final |
|
Re-inspection required |
10/31/24: GFCI required at Dishwasher, water hammer arrestor required at dishwasher, anti tip required at range, receptacle at laundry room required to be GFCI, water hammer arrestor required at laundry, exterior receptacle by water heater malfunctioning, Pressure relief valve shall terminate no higher than 6" or 2X the pipe diameter, water heater vents must be installed, ARC-fault breaker's required throughout at main panel, dryer vent must terminate with damper at T-top, provide access to roof. |
| 11/04/2024 |
COT - RSME - Mechanical Final |
|
Re-inspection required |
11/4/24: No access to house, called contractor and left message no answer. Needs to be rescheduled. |
| 11/15/2024 |
COT - RSME - Mechanical Final |
|
Passed |
passed |