Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.
| Date |
Description |
Inspector |
Results |
Comments |
| 04/01/2025 |
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
|
Re-inspection required |
4/1/25: seal all penetrations through vapor barrier, FHA plates required at dryer exhaust vent, thermostat must be 48" AFF, pex must be 12" away from can lights, seal all penetrations through top plate. |
| 04/03/2025 |
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
|
Re-inspection required |
4-3-25, lower thermostat height to 48" AFF and block using OSB, drywall, 2x4 where can lights are within 12" of pex lines. Another option would be to relocate the pex away from any can lights to provide the required clearance. Reinspection required |
| 04/04/2025 |
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
|
Passed |
4/4/2025 approved. all corrections have been made. |