Inspection Status: Passed

Inspection History: COT - RSPL - Rough Soil 

Permit Number - TC-RES-0623-05944

Inspection Description - COT - RSPL - Rough Soil 

Inspection Status - Passed

Date Description Inspector Results Comments
06/02/2025 COT - RSPL - Rough Soil  Passed Duplicate inspection. 6/2/2025
11/07/2023 COT - RSPL - Rough Soil  Re-inspection required Not ready. 2" shower line north of build is creating an S TRAP. The separation of the pipes need to be 2x's the pipe diameter from the edges not center of the pipe. 11/7/2023
11/08/2023 COT - RSPL - Rough Soil  Passed Not ready. 2" shower line north of build is creating an S TRAP. The separation of the pipes need to be 2x's the pipe diameter from the edges not center of the pipe. 11/7/2023
11/8/23: not per plan
11/27/2023 COT - RSPL - Rough Soil  Partial Pass 11/27/23: Laundry drain is going to be tied into bathroom group wet venting and this is not allowed per code (IRC P3108.1). as-built required. proceed at risk.
11/28/2023 COT - RSPL - Rough Soil  Passed Corrections were made. Rebar in footings per plan. Okay for concrete placement. 11/28/2023