Inspection Status: Passed

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Permit Number - TC-RES-0623-05944

Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Inspection Status - Passed

Date Description Inspector Results Comments
02/07/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 2/7/24: H2.5 clip's missing west wall first floor, verify 6x6 column at exterior wall and verify proper installation with Simpson HD2A, verify all interior baring walls have anchor bolts spaced 32"o.c, interior column footings missing Simpson CBSQ66, stairway is missing 4x12 at top of stairway connection, beam to beam connection not per plan, window openings not per plan revision is needed, inspection stopped due to rainy conditions more items may be added. Contractor sent a letter to verify all correction have been made. See letter in files. EWS