Inspection Status: Re-inspection required

Inspection History: BULD - Electrical Clearance

Permit Number - TC-RES-0623-05743

Inspection Description - BULD - Electrical Clearance

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
11/08/2023 BULD - Electrical Clearance Re-inspection required NR, main panel shall not be used as junction box for service panel of detached building, Polaris plug connections can be installed through the gutter,
*Note: the solar installation is per plan and can be cleared when main panel is corrected
11/13/2023 BULD - Electrical Clearance Passed Approved, DGC Clearance to TEP is required for the solar meter