Inspection Status: Not Ready
Inspection History: COT - RSEL - Electrical Final
| Date |
Description |
Inspector |
Results |
Comments |
| 07/24/2026 |
COT - RSEL - Electrical Final |
|
Not Ready |
7/24/2026 Not ready. Coat all exterior plastic pipes. Mini splits are not UL listed. Line sets need to be properly protected from UV. Condensation need to run further down. Disconnect for mini splits need to be readily accessible. Provide WR receptacles at all exterior locations. Riser has to be a misc of 7 3/4”. Landing has to be a minimum of 3’. Plumbing incomplete. Ensure receptacle underneath cabinet is GFCI protected. Lights not properly functioning in kitchen. Sub panel needs to have a 3’ clearance in front. Arc fault breakers are required at all living spaces. No foreign objects are aloud near sub panel. Stopped inspection. Other items may apply. |
| 07/28/2026 |
COT - RSEL - Electrical Final |
|
Re-inspection required |
|
| 10/02/2026 |
COT - RSEL - Electrical Final |
|
Not Applicable |
duplicate |