Permit: TC-RES-0526-02691

Parcel: 138080340


Addresses:

601 W CALLE ANTONIA

Inspection Status: Not Ready

Inspection History: COT - RSEL - Electrical Final 

Date Description Inspector Results Comments
07/29/2026 COT - RSEL - Electrical Final  Not Ready 07/29/2026
Not ready, call in at final. Add vapor barrier to T1.11 panel boards, replace stud on east wall that is not flush with top plate. Revise plans to reflect addition of mini-split and electrical load change.
08/25/2026 COT - RSEL - Electrical Final  Re-inspection required Not ready, outlets missing
09/01/2026 COT - RSEL - Electrical Final  Re-inspection required 9-1-26: per previous notes from inspection 7/29/26, an RFI for mechanical & electrical plan with load calculations is required. Also, show disconnect/subpanel on revision. Remove a section of drywall to inspect stud in question at the east side wall-see previous notes for information. Provide documentation for mini split- make sure it is UL Listed. Prior to covering drywall make sure to schedule a drywall screw inspection. All receptacles require covers, light fixtures must be installed for finals, and breakers must be properly labeled. When ready schedule all inspections.