| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/29/2026 | COT - RSEL - Outdoor Lighting | Not Ready | 07/29/2026 Not ready. Call in at final. Add outdoor lights that are covered on top to protect night sky and lightbulb not exposed. |
|
| 08/25/2026 | COT - RSEL - Outdoor Lighting | Re-inspection required | Not ready, outlets missing | |
| 09/01/2026 | COT - RSEL - Outdoor Lighting | Re-inspection required | 9-1-26: per previous notes from inspection 7/29/26, an RFI for mechanical & electrical plan with load calculations is required. Also, show disconnect/subpanel on revision. Remove a section of drywall to inspect stud in question at the east side wall-see previous notes for information. Provide documentation for mini split- make sure it is UL Listed. Prior to covering drywall make sure to schedule a drywall screw inspection. All receptacles require covers, light fixtures must be installed for finals, and breakers must be properly labeled. When ready schedule all inspections. |