Permit: TC-RES-0526-02674

Parcel: 141353430


Addresses:

6047 S JAKEMP TR

Inspection Status: Re-inspection required

Inspection History: COT - RSME - Mechanical Final 

Date Description Inspector Results Comments
06/03/2026 COT - RSME - Mechanical Final  Re-inspection required 6.3.26
Lockout caps required at refrigerant lines
Both units are over amped
07/14/2026 COT - RSME - Mechanical Final  Not Ready 07/14/2026
Corrections made to 6/3/26 inspection. Add a non-adhesive removable covering to protect refrigerant line R3 insulation - tape adhesive degrades foam - at line set coming from house to unit with wrapping or sheet metal. See IRC 2024 N1103.4.1 for code reference.

Technician can send photo to inspector: 520-739-9993.