Permit: TC-RES-0526-02454

Parcel: 120092910


Addresses:

232 E FAIRGROUND DR

Inspection Status: Re-inspection required

Inspection History: COT - BULD - SWG Clearance

Date Description Inspector Results Comments
05/12/2026 COT - BULD - SWG Clearance Re-inspection required 5-12-26: no contact information noted. Gates are locked and there is a "beware of dog" sign posted. I noted from the right of way that the system was not under test and the required tracer wire was missing on the gas line.
Note: a 15 pound gauge is required and the system shall be placed under test at 15psi for. Minimum of 10 minutes. Reschedule at your convenience.
05/14/2026 COT - BULD - SWG Clearance Passed 5/14/26: SWG CLEARANCE APPROVED. OK TO BACKFILL