Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Parcel: 117022230


Addresses:

103 E 2ND ST


Inspection Status: Re-inspection required

Inspection History: RSPL - Plumbing Progress

Permit Number - TC-RES-0525-02753

Inspection Description - RSPL - Plumbing Progress

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
05/30/2025 RSPL - Plumbing Progress Re-inspection required secure pex lines in crawl space at every 32” horizontally. properly insulate water lines in crawl space and at all exterior with 10 mil tape. add hammer arrestor at hot line for dishwasher. 5/30/2025
06/03/2025 RSPL - Plumbing Progress Partial Pass per section M1801.10 vents shall be supported not exceeding 4’ with no more than 1’ of unsupported vertical rise above roof. water lines at casita area need to properly insulated and taped. 6/3/2025
06/04/2025 RSPL - Plumbing Progress Not Ready
06/09/2025 RSPL - Plumbing Progress Passed