Parcel: 117022230


Addresses:

103 E 2ND ST


Inspection Status: Re-inspection required

Inspection History: COT - RSPL - Plumbing Final 

Permit Number - TC-RES-0525-02753

Inspection Description - COT - RSPL - Plumbing Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
05/30/2025 COT - RSPL - Plumbing Final  Re-inspection required secure pex lines in crawl space at every 32” horizontally. properly insulate water lines in crawl space and at all exterior with 10 mil tape. add hammer arrestor at hot line for dishwasher. 5/30/2025
06/03/2025 COT - RSPL - Plumbing Final  Partial Pass per section M1801.10 vents shall be supported not exceeding 4’ with no more than 1’ of unsupported vertical rise above roof. water lines at casita area need to properly insulated and taped. 6/3/2025
06/04/2025 COT - RSPL - Plumbing Final  Not Ready
06/10/2025 COT - RSPL - Plumbing Final  Passed