Inspection Status: Passed

Inspection History: COT - RSOL - Electrical Final Solar Project

Date Description Inspector Results Comments
01/08/2026 COT - RSOL - Electrical Final Solar Project Passed 1.8.26
Approved for BAT code to TEP
10/09/2025 COT - RSOL - Electrical Final Solar Project Re-inspection required 10.9.2025
Plan calls for #8 grounding wires to the Storz batteries - unable to verify equipment grounded.
11/06/2025 COT - RSOL - Electrical Final Solar Project Re-inspection required Not ready - did not meet deadline of 330pm
12/04/2025 COT - RSOL - Electrical Final Solar Project Canceled 12.04.225
Canceled by contractor.