Inspection Status: Re-inspection required
Inspection History: COT - RSME - Mechanical Final
| Date |
Description |
Inspector |
Results |
Comments |
| 05/15/2025 |
COT - RSME - Mechanical Final |
|
Re-inspection required |
5-15-25, condenser is over amped-condenser calls for a maximum 40 amp breaker and currently installed at panel is a 50. Replace breaker to a 40 amp. |
| 06/05/2025 |
COT - RSME - Mechanical Final |
|
Passed |
6-5-25: mechanical final approved. |