Permit: TC-RES-0525-02457

Parcel: 140566020


Addresses:

6847 S BENEDETTI CT

Inspection Status: Re-inspection required

Inspection History: COT - RSME - Mechanical Final 

Date Description Inspector Results Comments
05/15/2025 COT - RSME - Mechanical Final  Re-inspection required 5-15-25, condenser is over amped-condenser calls for a maximum 40 amp breaker and currently installed at panel is a 50. Replace breaker to a 40 amp.
06/05/2025 COT - RSME - Mechanical Final  Passed 6-5-25: mechanical final approved.