Inspection History Details
Inspection Status: Not Ready
Inspection History: COT - RSEL - Electrical Underground
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/31/2025 | COT - RSEL - Electrical Underground | Not Ready | 7.31.25 Not ready Called Waited 15 mins on site No contact |
|
| 08/01/2025 | COT - RSEL - Electrical Underground | Re-inspection required | 8.1.25 Trench is half way refilled unable to see or access underground work to verify depth of conduit or material used. Site also blocked by scaffolding. Site must be readily accessible and underground conduit must be visible and exposed. |
|
| 08/05/2025 | COT - RSEL - Electrical Underground | Re-inspection required (with fee) | 8/5/25 underground conduit not at proper depth, currently sits at 10 inches from top of pipe, pvc should be at 18 inches from top of conduit | |
| 08/06/2025 | COT - RSEL - Electrical Underground | Passed | ||
| 08/06/2025 | COT - RSEL - Electrical Underground | Passed | 8.56.25 Approved |