Permit: TC-RES-0525-02409

Parcel: 12617106A


Addresses:

550 S LONGFELLOW AV

Inspection Status: Not Ready

Inspection History: COT - RSEL - Electrical Underground 

Date Description Inspector Results Comments
07/31/2025 COT - RSEL - Electrical Underground  Not Ready 7.31.25
Not ready
Called
Waited 15 mins on site
No contact
08/01/2025 COT - RSEL - Electrical Underground  Re-inspection required 8.1.25
Trench is half way refilled unable to see or access underground work to verify depth of conduit or material used. Site also blocked by scaffolding. Site must be readily accessible and underground conduit must be visible and exposed.
08/05/2025 COT - RSEL - Electrical Underground  Re-inspection required (with fee) 8/5/25 underground conduit not at proper depth, currently sits at 10 inches from top of pipe, pvc should be at 18 inches from top of conduit
08/06/2025 COT - RSEL - Electrical Underground  Passed
08/06/2025 COT - RSEL - Electrical Underground  Passed 8.56.25
Approved