Permit: TC-RES-0524-02970

Parcel: 129091670


Addresses:

1820 S CHERRY AV

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.

Date Description Inspector Results Comments
08/22/2024 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Re-inspection required Window seal has to be brought down to 44" max for means of egress. Provide combination smoke detector outside of bedroom. Provide exhaust fan in laundry room area. Water heater needs sediment trap, 2 openings for ventilation, solid piping for TMP, pan, and vent going through room with a minimum of 1" clear from combustible. Missing receptacle in kitchen area above single counter top. Replace outside wires in back patio due to outdoor weather exposure. Replace schedule 40 pipe feeding existing meter to new 200 amp panel, secure and provide conduit. 8/22/2024
10/18/2024 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Passed