Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Excavation/Rebar/Zoning
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/01/2026 | COT - RSBU - Excavation/Rebar/Zoning | Re-inspection required | 5.1.26 1. Vertical reinforcements too far apart 48" is max 2. Rebar too close to dirt through out. 3. Porch slab not done 4. Garage slab not done 5. Missing B/S3 detail at new foundation stem adjacent to existing. ****Stopped inspection. More items maybe added on reinspect.***** |
|
| 05/09/2025 | COT - RSBU - Excavation/Rebar/Zoning | Partial Pass | Footings for interior load bearing wall. Ok to place concrete in progress area. | |
| 05/26/2026 | COT - RSBU - Excavation/Rebar/Zoning | Passed |