Permit: TC-RES-0523-05469

Parcel: 123070310


Addresses:

2327 E MABEL ST

Inspection Status: Partial Pass

Inspection History: RSBU - Building Final 

Date Description Inspector Results Comments
04/17/2025 RSBU - Building Final  Partial Pass Ok to move in furniture and custom cabinets.
07/03/2025 RSBU - Building Final  Re-inspection required 7/3/25
1. Laundry receptacles need to be GFCI protected
2. Dishwasher receptacle/garbage disposal needs to be GFCI protected
3. Loose receptacle in bedroom play hallway/adjacent to bathroom, loose receptacles in bedroom area.
4. Water heater t/p line has a cut in the line, also terminate line 2-6" above grade
5. Outdoor receptacles are exposed, needs to sit flush inside wall.
6. Bigger HVAC has oversized breakers, max is 40A and is currently on a 60A breaker and 45A fuse.
7. Missing Site Address. The address identification shall be legible and placed in a position that is visible from the street or road fronting the property. Address identification characters shall contrast with their background. Address numbers shall be Arabic numbers or alphabetical letters. Each character shall be not less than 4 inches in height with a stroke width of not less than 0.5 inch.

8. Mini split is not labeled in the main panel.
07/08/2025 RSBU - Building Final  Passed