Inspection Status: Not Ready
Inspection History: COT - RSEL - Electrical Final
| Date |
Description |
Inspector |
Results |
Comments |
| 01/02/2024 |
COT - RSEL - Electrical Final |
|
Not Ready |
|
| 01/08/2024 |
COT - RSEL - Electrical Final |
|
Not Ready |
1/8/24: Not ready |
|
COT - RSEL - Electrical Final |
|
Re-inspection required |
6/26/24: missing address plaque. Clean outs need to be cut to grade. Paint vent pvc on roof. Laundry receptacle not GFCI protected. Arc fault protected breakers needed for all living spaces in main panel. Paint pvc clean out for laundry room exterior. Missing interconnected smoke detectors throughout house in bedrooms and outside of sleeping quarters. |
| 06/28/2024 |
COT - RSEL - Electrical Final |
|
Passed |
|