Permit: TC-RES-0523-05012

Parcel: 133130790


Addresses:

7822 E LEE ST

Inspection Status: Re-inspection required

Inspection History: COT - RSME - Mechanical Final 

Date Description Inspector Results Comments
06/23/2023 COT - RSME - Mechanical Final  Re-inspection required 6/23/23: remove deteriorated line-set insulation at the compressor and wrap with UV-resistant tape. Secure non-metallic conduit to disconnect. Maintain min 1"clearance of insulation or combustible materials to furnace vents.
08/02/2023 COT - RSME - Mechanical Final  Canceled Canceled per contractor. Prefer on-site inspection. 8/2/2023
08/09/2023 COT - RSME - Mechanical Final  Re-inspection required (with fee) 6/23/23: remove deteriorated line-set insulation at the compressor and wrap with UV-resistant tape. Secure non-metallic conduit to disconnect. Maintain min 1"clearance of insulation or combustible materials to furnace vents.

Canceled per contractor. Prefer on-site inspection. 8/2/2023
8/9/23: all exterior line set insulation is required to be protected with "UV-resistant tape" . 10 mil tape is not UV-resistant. Maintain minimum 1" clearance from furnace exhaust to all combustibles. 3rd failed inspection, pay a re-fee before scheduling next inspection.
09/22/2023 COT - RSME - Mechanical Final  Passed