Inspection Status: Re-inspection required
Inspection History: COT - RSPL - Plumbing Final
| Date |
Description |
Inspector |
Results |
Comments |
| 03/13/2025 |
COT - RSPL - Plumbing Final |
|
Re-inspection required |
3/13/25: receptacle spacing at bedrooms and kitchen not code compliant, GFCI required under sink and laundry room, light fixtures must be installed at final, all cover plates must be installed, all receptacles within 6' of water supply must be GFCI, HVAC being over amped, all exterior plastic piping must be coated.Roofing not complete. NOT READY |
| 03/24/2025 |
COT - RSPL - Plumbing Final |
|
Passed |
|