Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
The login landing page when selecting 'View' is still occurring and is still pending further investigation.
Inspection Status: Re-inspection required
Inspection History: COT - RSEL - Outdoor Lighting
| Date |
Description |
Inspector |
Results |
Comments |
| 03/13/2025 |
COT - RSEL - Outdoor Lighting |
|
Re-inspection required |
3/13/25: receptacle spacing at bedrooms and kitchen not code compliant, GFCI required under sink and laundry room, light fixtures must be installed at final, all cover plates must be installed, all receptacles within 6' of water supply must be GFCI, HVAC being over amped, all exterior plastic piping must be coated.Roofing not complete. NOT READY |
|
COT - RSEL - Outdoor Lighting |
|
Passed |
|