Inspection History Details
Inspection Status: Canceled
Inspection History: COT - RSEL - Electrical Final
Permit Number - TC-RES-0523-04900
Inspection Description - COT - RSEL - Electrical Final
Inspection Status - Canceled
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/29/2023 | COT - RSEL - Electrical Final | Canceled | ||
| 10/03/2023 | COT - RSEL - Electrical Final | Re-inspection required | 10/3/23: verify max number of wires in attic junction box (missing cover), circuit 9 (master bedroom) is tied into circuit 5 kitchen lights and refrigerator, circuit 10 (bedroom #2 is tied into circuit 9 hall light and circuit 3 at kitchen counter. Water hammer arrestor missing at refrigerator, laundry and dishwasher. Whip at water heater not secure on coupling. A/C unit needs p-trap at condensate line and needs to be supported on treated lumber. Panel schedule needs to be reviewed and replaced circuits are missing and tied together. | |
| 10/10/2023 | COT - RSEL - Electrical Final | Passed | 10/10/23: all corrections made |