Inspection Status: Canceled
Inspection History: COT - RSPL - Plumbing Final
| Date |
Description |
Inspector |
Results |
Comments |
| 09/29/2023 |
COT - RSPL - Plumbing Final |
|
Canceled |
|
| 10/03/2023 |
COT - RSPL - Plumbing Final |
|
Re-inspection required |
10/3/23: verify max number of wires in attic junction box (missing cover), circuit 9 (master bedroom) is tied into circuit 5 kitchen lights and refrigerator, circuit 10 (bedroom #2 is tied into circuit 9 hall light and circuit 3 at kitchen counter. Water hammer arrestor missing at refrigerator, laundry and dishwasher. Whip at water heater not secure on coupling. A/C unit needs p-trap at condensate line and needs to be supported on treated lumber. Panel schedule needs to be reviewed and replaced circuits are missing and tied together. |
| 10/10/2023 |
COT - RSPL - Plumbing Final |
|
Passed |
10/10/23: all corrections made |