Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Canceled
Inspection History: RSBU - Building Final
Permit Number - TC-RES-0523-04900
Inspection Description - RSBU - Building Final
Inspection Status - Canceled
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/29/2023 | RSBU - Building Final | Canceled | ||
| 10/03/2023 | RSBU - Building Final | Re-inspection required | 10/3/23: verify max number of wires in attic junction box (missing cover), circuit 9 (master bedroom) is tied into circuit 5 kitchen lights and refrigerator, circuit 10 (bedroom #2 is tied into circuit 9 hall light and circuit 3 at kitchen counter. Water hammer arrestor missing at refrigerator, laundry and dishwasher. Whip at water heater not secure on coupling. A/C unit needs p-trap at condensate line and needs to be supported on treated lumber. Panel schedule needs to be reviewed and replaced circuits are missing and tied together. | |
| RSBU - Building Final | Passed |