Permit: TC-RES-0523-04900

Parcel: 12212072D


Addresses:

4407 E BELLEVUE ST

Inspection Status: Canceled

Inspection History: COT - RSME - Mechanical Final 

Date Description Inspector Results Comments
09/29/2023 COT - RSME - Mechanical Final  Canceled
10/03/2023 COT - RSME - Mechanical Final  Re-inspection required 10/3/23: verify max number of wires in attic junction box (missing cover), circuit 9 (master bedroom) is tied into circuit 5 kitchen lights and refrigerator, circuit 10 (bedroom #2 is tied into circuit 9 hall light and circuit 3 at kitchen counter. Water hammer arrestor missing at refrigerator, laundry and dishwasher. Whip at water heater not secure on coupling. A/C unit needs p-trap at condensate line and needs to be supported on treated lumber. Panel schedule needs to be reviewed and replaced circuits are missing and tied together.
10/10/2023 COT - RSME - Mechanical Final  Passed 10/10/23: all corrections made