Inspection Status: Not Ready

Inspection History: RSBU - Building Final 

Date Description Inspector Results Comments
01/22/2025 RSBU - Building Final  Not Ready Please install heating and cooling mini split as per plan and Hilow combustion air relief for water heater
06/03/2025 RSBU - Building Final  Re-inspection required Please install heating and cooling mini split as per plan and Hilow combustion air relief for water heater
6/3/25: Receptacle spacing not per plan, combustion air for water heater not per plan, window sill height not code complaint, Exterior receptacles over by mini splits must be WR GFCI and must have approved cover, insulation at refrigerant lines must be wrapped and protected from UV, Disconnect boxes must be properly secured and cover plates must be installed at time of inspection, fuses were not verified due to cover plates missing and loose connections, please label disconnect boxes, mini splits must be 3" above grade, condensation missing at east unit. Exterior Plastic piping must be coated for UV protection, label breakers to correspond with new rooms, construction was completed and covered prior to inspections being called in. We will have to verify framing, electrical, and all new construction prior to issuance of CofO.
11/07/2025 RSBU - Building Final  Passed