Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Masonry Pregrout
| Date |
Description |
Inspector |
Results |
Comments |
| 06/05/2025 |
COT - RSBU - Masonry Pregrout |
|
Re-inspection required |
6/5/25: site plan must correctly identify the new section of the 50' CMU wall. Detail for rebar reinforcement required, Overlap for #4 rebar shall be no less then 24", rebar reinforcement must be supported 3" off of ground and support must be coated or wrapped with 10 mil tape. |
| 06/10/2025 |
COT - RSBU - Masonry Pregrout |
|
Not Ready |
|
| 06/25/2025 |
COT - RSBU - Masonry Pregrout |
|
Partial Pass |
Partial pass. 1st lift approved okay to grout. 7/25/2025 |