Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Firewall/Fire Barrier/Firestop
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/30/2026 | COT - RSBU - Firewall/Fire Barrier/Firestop | Re-inspection required | 1-30-26: owner's plans do not have city approved stamp, therefore, inspections were not completed. Owner was advised to contact someone in plan review for plan status. | |
| 02/10/2026 | COT - RSBU - Firewall/Fire Barrier/Firestop | Re-inspection required | 2-10-26: framing at fire rated wall not per plans. Install 2x6 studs @ 16" o.c., shot pins are required within 6" at the end of each plate, plans also call for mineral wool insulation and currently installed is R13. Either install per approved plans or submit a revision showing type of insulation. Properly seal all gaps at ceiling & submit a revision for electrical receptacles at firewall. | |
| 04/14/2026 | COT - RSBU - Firewall/Fire Barrier/Firestop | Partial Pass | 04/14/2026 Corrections made to prior inspection. Verified electrical rough-in at firewall, 2x6 studs, mineral wool insulation. Okay to proceed. Partial pending final 5/8" type-x gypsum on both sides and nail schedule. |
|
| 09/30/2026 | COT - RSBU - Firewall/Fire Barrier/Firestop | Passed | 09/30/2026 Verified revision and assembly at firewall, nail schedule. Okay to tape and texture. |