Inspection History Details
Inspection Status: Passed
Inspection History: RSBU - Building Final
Permit Number - TC-RES-0425-01702
Inspection Description - RSBU - Building Final
Inspection Status - Passed
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/06/2026 | RSBU - Building Final | Passed | OK to occupy. | |
| 12/24/2025 | RSBU - Building Final | Re-inspection required | 12.24.25 Missing GFCI at laundry room Missing hammer arrester at hot line to dishwasher Address missing Breakers to livable spaces must be arc fault Need to verify fuses at ac disconnect (Current fuses are weathered and unreadable) |