Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Preslab
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/24/2025 | COT - RSBU - Preslab | Re-inspection required | 6/24/25: reinforcement must maintain 3" clearance from earth, footing depth not per approved plans 12" min, reinforcement at existing concrete slabs was never verified prior to concrete placement (please verify reinforcement via documentation or third party report), revision required for proper documentation and details on dowels required from existing slab to new portion of slab at AZ room. Re-inspection required. | |