Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Passed
Inspection History: COT - RSPL - Plumbing FinalĀ
| Date |
Description |
Inspector |
Results |
Comments |
| 04/29/2024 |
COT - RSPL - Plumbing FinalĀ |
|
Passed |
Re-piping is complete to upstairs and downstairs bathrooms, kitchen, laundry room, garage for water heater and front/rear hose bibs. Okay to proceed with patching, repairing damaged drywall in walls and ceilings. |